Air Pressure + temperature + humidity: Primarily used in environments with high cleanliness requirements, such as operating rooms, clean workshops, cleanrooms, and laboratories.
2-channel digital input (DI): Accepts dry contact signals for monitoring the status of devices such as door magnets, water leak sensors.
1-channel RS485 to Ethernet: Acts as a protocol conversion gateway, using devices such as Modbus RTUs (e.g., electricity meters, water meters, traditional sensors) to Ethernet for system integration.
1-channel relay output (DO): Functions normally open (NO) / normally closed (NC) contacts for programmable control of external devices. Automatically and intelligently activates/deactivates devices such as fans, alarms, or lights based on threshold violations.
Ethernet Communication: 10/100M auto-adaptive Ethernet interface, supporting multiple network protocols including MQTT, SNMP, Modbus TCP, and UDP, facilitating integration into existing LANs.
PoE Power (802.3af): Supports power supply via Ethernet cable, eliminating the need for separate power wiring. This simplifies installation in challenging locations such as ceilings or confined spaces. A standard DC power interface is reserved as a backup.
Local Data Logging: The device has built-in memory capable of storing 100,000 data records, enabling cyclical recording of historical data for easy tracing and analysis.
Multiple Alarm Mechanisms: Allows users to independently set high/low alarm thresholds for each monitored parameter. Supports various alarm methods, including local sound/light indicators, email notifications, or SNMP traps.
Wide Temperature and Voltage Range Design: Reliably operates over a wide temperature range of -20 °C to 65 °C and in complex industrial electromagnetic environments.
Rugged Housing: Constructed from a metal or high-strength flame-retardant plastic housing, providing superior shielding and durability.
| Measurement Content | Temperature, Humidity, Dew Point, Atmospheric Pressure |
| Measurement Range |
Temperature -25~80℃, Humidity 0~99.9%RH (Non-Condensing) 300~1100 hPa (equivalent to +9000m to -500m above sea level) |
| Operating Environment | Temperature -25~65℃, Humidity 0~99.9%RH (Non-Condensing) |
| Measurement Accuracy |
Temperature ±0.2℃ (at 25℃); Humidity ±2%RH (at 25℃) Atmospheric ±0.12 hPa (equal that ±1m, at 700~900hPa) |
| Power Supply | DC12~48V, POE power supply |
| Communication Protocol | Modbus TCP, UDP, SNMP (V1.V2), MQTT |
| Communication Interface | RJ45 |
| Equipment Interface |
2 channels DI input, 1 channel DO output, 1 channel RS485, 1 channel DC12V output |
| Alarm | Light, sound, email alarm |
| Screen Display | 3.5 inch TFT color screen |
| Data Storage | 100,000 records |
| Installation | Screw fixation, Magnetic |
| Dimensions | 100*172*34mm |
The sensor monitors core environmental parameters including temperature, humidity, dew point, and atmospheric pressure. It is ideal for cleanrooms, laboratories, clean workshops, and operating rooms.
Yes, it supports standard PoE (802.3af) power supply, allowing data and power transmission over a single Ethernet cable. A standard DC 12-48V power interface is also reserved as a backup.
The device features built-in memory capable of storing up to 100,000 historical data records locally, which enables cyclical recording for easy analysis and tracing.
It supports RJ45 Ethernet communication with protocols including Modbus TCP, UDP, SNMP (V1/V2), and MQTT. It also includes an RS485 interface which acts as a protocol gateway to integrate Modbus RTU devices.
The sensor allows users to independently set high/low thresholds for each parameter. When thresholds are breached, it triggers local sound and light indicators, email notifications, or SNMP traps.
Yes. The sensor is equipped with a 1-channel relay output (DO) featuring normally open (NO) and normally closed (NC) contacts, enabling programmable control to automatically trigger external devices like fans, alarms, or lights based on threshold violations.